ERV (4,000 to 11,500 CFM)

ERV5000i/e, ERV6500i/e, ERV8000i/e, ERV10000i/e

Indoor Energy Recovery VentilatorVenmar CES’s larger Energy Recovery Ventilators (ERVs), from 4,000 to 11,500 cfm, offer everything you would expect in a standard energy recovery ventilator, but incorporate some high end features that allow this product to compete favourably against what would otherwise be a custom product.

Venmar CES Energy Recovery Ventilators (ERV) are manufactured with a high performance enthalpy wheel, certified to AHRI Standard 1060, that transfers total energy (in the form of heat and moisture) between the outdoor and exhaust airstreams. The ERV series provide a cost-effective ventilation solution that is ideal for delivering 100% fresh, outdoor air while reducing the mechanical heating, cooling and humidification requirements of the space. This improves overall space humidity and control for superior Indoor Air Quality (IAQ) and occupant satisfaction.

In addition, Venmar CES ERVs in this category feature a number of high end features that make it extremely attractive and competitive in the custom commercial and air handling markets.

A variety of post conditioning technologies such as hot water, steam or electric heat and chilled water or (split) Dx for cooling.

The cabinet is fabricated from a robust double wall, no-through-metal cabinet and thermally broken doors as standard along with an Impermium™ membrane floor that provides a non-slip air and water-tight barrier which eliminates the need to tread plate floors. The package can be rounded out with optional Venmar CES DDC Controls and up to MERV 17 filters on the supply and return.

Unit Model
Airflow
Indoor Dimensions (L x W x H)
Outdoor Dimensions (L x W x H)
ERV5000i/e
4,000–5,500 CFM
[1,888–2,596 l/s]
117”* x 84” x 70”
[2,972* x 2,134 x 1,778 mm]
117”* x 84” x 70”
[2,972* x 2,134 x 1,778 mm]
ERV6500i/e
5,000–7,000 CFM
[2,360–3,304 l/s]
117”* x 88” x 78”
[2,972* x 2,234 x 1,982 mm]
117”* x 88” x 78”
[2,972* x 2,234 x 1,982 mm]
ERV8000i/e
6,000–9,000 CFM
[2,832–4,248 l/s]
127”* x 95” x 90”
[3,226* x 2,413 x 2,286 mm]
127”* x 95” x 90”
[3,226* x 2,413 x 2,286 mm]
ERV10000i/e
8,000–11,500 CFM
[3,776–5,428 l/s]
139”* x 103” x 108”
[3,531* x 2,616 x 2,743 mm]
139”* x 103” x 108”
[3,531* x 2,616 x 2,743 mm]
*Note: Minimum unit length given. Unit length is dependent upon options selected (please add 38 to overall length for heating/cooling coil; add 18 if additional access is required between coils). Contact your local Venmar CES representative for more specific dimensions and guidance.